SECTION 08360
OVERHEAD DOORS
Display hidden notes to specifier. (Don't know how? Click Here)
** NOTE TO SPECIFIER ** Clopay sectional overhead doors, insulated and
non-insulated.
This section is based on the products of Clopay Building Products
Company, which is located at:
Clopay Building Products
8585 Duke Blvd
Mason, OH 45040
Tel: 800-526-4301 prompt #3
Fax: 888-434-3193
Email: [email protected]
Web: www.clopaycommercial.com
[ Click Here ] for additional information.
Clopay entered the commercial and industrial upward acting door
industry in 1966. For over 3 decades, Clopay has been providing the
commercial sectional and coiling steel door market with creative
solutions, innovative products, and superior customer service. With
its emphasis on innovative design and application, combined with a
unique combination of two trusted brands -- Clopay, and Ideal Door --
Clopay Building Products Company is distinguished from all its
competitors.
1.
GENERAL
1.
SECTION INCLUDES
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this
project; add others as required.
A.
Insulated steel sandwich sectional overhead door (Model 3724)
B.
Electric Door Operators
2.
RELATED SECTIONS
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this
project; add others as required.
A.
03 30 00 - Cast-In-Place Concrete.
B.
04 20 00 - Unit Masonry Assemblies.
C.
05 50 00 - Metal Fabrications.
D.
06 10 00 - Rough Carpentry.
E.
07 90 00 - Joint Seals.
F.
08 71 00 - Door Hardware and locks.
G.
09 90 00 - Paints and Coatings.
H.
11 15 00 - Parking Control Equipment: Remote door control.
I.
16 05 00 - Electrical service and connections for powered
operators.
3.
REFERENCES
** NOTE TO SPECIFIER ** Delete references from the list below that are
not actually required by the text of the edited section.
A.
ASTM B 653/653M
B.
ASTM B 209/209M
C.
ASTM B 221/221M
D.
AAMA 2604
E.
DASMA TDS-163
F.
ANSI/DASMA 102
1.
SUBMITTALS
A.
Submit under provisions of Section 01 30 00 - Administrative
Requirements.
B.
Product Data: Manufacturer's data sheets on each product to
be used, including:
1.
Preparation instructions and recommendations.
2.
Storage and handling requirements and recommendations.
3.
Installation methods.
4.
Operation and maintenance data.
** NOTE TO SPECIFIER ** Delete below if electrically operated doors
not required.
5.
Nameplate data and ratings for motors.
A.
Shop Drawings: Include opening dimensions and required
tolerances, connection details, anchorage spacing, hardware
locations, and installation details.
B.
Selection Samples: Upon request furnish color samples or 2’ X
2’ section sample.
1.
WIND PERFORMANCE REQUIREMENTS
A.
Design doors to withstand positive and negative wind loads
as calculated in accordance with applicable building code
and detailed in structural documents.
** NOTE TO SPECIFIER ** If the two paragraphs below are retained, be
careful not to specify specific doors in Part 2 that could conflict
with these requirements. Instead, select door types required and leave
specific door thickness and gauge to manufacturer.
6.
QUALITY ASSURANCE
A.
Manufacturer Qualifications: Minimum ten years of documented
experience.
B.
Installer Qualifications: Minimum five years of documented
experience, and authorized by the door manufacturer.
1.
WARRANTY
A.
Manufacturers Limited Warranty steel sectional overhead
doors.
** NOTE TO SPECIFIER ** Retain paragraphs above and below for steel
doors.
1.
Standard finish warranty against cracking, checking, or
peeling for 10 years.
Custom color option Color Blast Finish limited warranty period for 5
years;
Delamination warranty for 10 years; Parts and Hardware for 1 year.
Extended 8-Year Hardware Warranty option.
2.
PRODUCTS
1.
MANUFACTURERS
A.
Acceptable Manufacturer: Clopay Corporation: 8585 Duke
Blvd.; Mason, OH 45040; https://www.clopaydoor.com
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs;
coordinate with requirements of Division 1 section on product options
and substitutions.
B.
Substitutions: Not permitted.
C.
Requests for substitutions will be considered in accordance
with provisions of Section 01 60 00 - Product Requirements.
** NOTE TO SPECIFIER ** Delete door type and models not required.
2.
LIGHT RIBBED STEEL DOORS, THERMALLY-BROKEN, POLYURETHANE
INSULATED
A.
Door Construction:
1.
Panels: Foamed in place Polyurethane core construction
between exterior and interior steel skins.
2.
Steel Skins: Formed from roll formed commercial or
drawing quality steel sheet, hot-dip galvanized per ASTM
A 924/A 924M and ASTM A 653/A 653M, pre-painted with
primer and baked-on polyester topcoat; sections formed
to create weather tight tongue-in-groove meeting joint.
3.
Reinforcing: Galvanized and primed steel reinforcement
located under each hinge location, pre-punched for hinge
attachment.
B.
Premium Duty 2-inches (51 mm) Door: Clopay Model 3724.
1.
Style: Steel doors with minor ribs, thermally-broken,
polyurethane insulated.
2.
Maximum Door Size: 32 feet, 2 inches (9.8 m) wide by 26 feet
(7.9 m) high.
3.
Overall Panel Thickness: 2-inches (51 mm).
4.
Steel Skin Thickness: Minimum 24 gauge 0.022 inch (0.40 mm)
exterior; minimum 27 gauge 0.016 inch (0.40 mm) interior.
5.
End Stiles: Galvanized steel end stiles, engineered for easy
hardware attachment through pre-punched holes. Minimum 18
gauge, 0.045 inch (1.14 mm) thick for single end hinge style
and 16 gauge .056 inch (1.42 mm) minimum for double end
hinge style.
6.
Astragal: U-shaped flexible PVC in retainer of full-length
0.055 inch (1.4 mm) rigid PVC.
7.
Thermal Resistance (R-value): 18.4 deg F hr sq ft/Btu (3.0
(K sq m)/W); calculated door section R-value in accordance
with DASMA TDS-163.
8.
Insulation: CFC-free and HCFC-free polyurethane, fully
encapsulated
9.
U-Factor: 0.16
10.
Air Infiltration: .022 cfm @ 25 mph
** NOTE TO SPECIFIER ** Window and glazing paragraphs below are
optional. Delete options not required.
11.
Windows: None.
12.
Windows: Extruded polypropylene windows measuring 8 inches
by 24 inches (200 mm by 600 mm).
a.
Glazing: 1 inch nominal (25 mm) insulated glass.
b.
Glazing: 1 inch nominal (25 mm) insulated tempered
glass.
c.
Glazing: 1/4 inch (6 mm) impact resistant Lexan.
13.
Windows: Extruded polypropylene windows measuring 12 inches
by 24 inches (305 mm by 600 mm).
a.
Glazing: 1 inch nominal (25 mm) insulated glass.
b.
Glazing: 1 inch nominal (25 mm) insulated tempered
glass.
c.
Glazing: 1/4 inch (6 mm) impact resistant Lexan.
14.
Windows: Full vision aluminum section, pre-painted to match
door finish.
a.
Glazing: 1/8 inch (3 mm) DSB glass
b.
Glazing: 1/4 inch (6 mm) tempered glass
c.
Glazing: 1/2 inch (13 mm) insulated glass
d.
Glazing: Custom ___________________
15.
Windows: Black extruded polypropylene windows with rounded
corners measuring 13 inches by 26 inches (303 mm by 606 mm).
a.
Glazing: 5/8 inch (16 mm) double pane acrylic.
b.
Glazing: 5/8 inch (16 mm) double pane lexan.
16.
Finish: Interior stucco embossed texture with shallow U
ribbed pattern, white interior color. Exterior stucco
embossed with ribbed pattern, exterior as follows:
** NOTE TO SPECIFIER ** Delete color not required.
a.
White.
b.
Brown.
c.
Commercial Tan
d.
Commercial Gray
e.
Trinar White
f.
Black
g.
Clopay ColorBlast®, a two part paint system utilizing
Sherwin Williams® Solar reflective Polane Paint system.
Sherwin Williams® color number SW ______.
1.
Locking:
** NOTE TO SPECIFIER ** Delete lock type not required.
a.
Provide one inside slide lock.
b.
Provide two inside slide locks.
c.
Provide five pin cylinder lock with outside key
d.
No lock
** NOTE TO SPECIFIER ** Drop door safety devices is optional and
available on vertical, high lift and follow the track types only.
Delete if not required.
18.
Door Drop Safety Device: Provide brackets designed to stop
the fall of the door should lift cables fail.
19.
Weatherstripping: Provide complete perimeter seals. Provide
flexible top seal, flexible jamb seal and U shaped bottom
seal.
20.
Track:
** NOTE TO SPECIFIER ** Delete track sizes not required.
a.
2 inches (50 mm) track designed for 2” diameter rollers.
Vertical tracks minimum 0.061 inch (1.55 mm) galvanized
steel. Horizontal tracks minimum 0.075 inch (1.91 mm)
galvanized steel.
b.
3 inches (75 mm) track designed for 3” diameter rollers.
Vertical and horizontal tracks minimum 0.096 inch (2.43
mm) galvanized steel.
c.
Provide track configuration to maximize headroom available
per plans.
1.
Spring Counterbalance: Torsion spring counterbalance
mechanism sized to weight of the door, with with high
strength galvanized aircraft cable with minimum 7 to 1
safety factor.
** NOTE TO SPECIFIER ** Delete spring quality not required.
a.
Standard Cycle Spring: 10,000 cycle.
b.
High Cycle Spring: 25,000 cycles.
c.
High Cycle Spring: 50,000 cycles.
d.
High Cycle Spring: 100,000 cycles.
e.
Maximum cycles on a single shaft line
** NOTE TO SPECIFIER ** Delete if not required.
22.
Break-Away Bottom Section: Integral part of door; with
fiberglass or 1/8 inch (3 mm) polycarbonate lined bottom
section with flexible neoprene rubber side edges; exterior
to match door face.
** NOTE TO SPECIFIER ** Delete type not required.
a.
Single breakaway bottom section for doors up to 20 feet (6
m) wide.
b.
Double breakaway bottom section for doors up to 14 feet
(4.3 m) wide.
23. Pass Door (Walk-Through Service Door): Integral part of door; 32
inches (813 mm) by 80 inches (2032 mm) with aluminum frame, geared
hinge, and pneumatic door closer; exterior matching door face;
integral shiplap weather seal; keyed dead latch security lock
** NOTE TO SPECIFIER ** Delete if not required.
3.
ELECTRIC DOOR OPERATORS
A.
General: Provide electric door operator provided by door
manufacturer for door with operational life specified
complete with electric motor and factory pre-wired motor
controls, starter, gear-reduction unit, clutch,
remote-control stations, control devices, integral gearing
for locking door, and accessories required for proper
operation. Comply with NFPA 70.
** NOTE TO SPECIFIER **Delete following option if not required. Brake
is standard on openers with 3/4 HP or more.
1.
Solenoid-operated brake.
A.
Disconnect Device: Provide hand-operated disconnect or
mechanism for emergency manual operation while disconnecting
motor, without affecting timing of limit switch. Mount
disconnect and operator so they are accessible from floor
level. Include interlock device to automatically prevent motor
from operating when emergency operator is engaged.
B.
Design operator so motor may be removed without disturbing
limit switch adjustment and without affecting emergency
auxiliary operator.
C.
Provide control equipment complying with NEMA ICS1, NEMA ICS
2, and NEMA ICS 6, with NFPA 70 Class 2 control circuit,
maximum 24-V, AC or DC.
D.
Electric Motors: Provide high-starting torque, reversible,
continuous-duty, Class A insulated, electric motor, complying
with NEMA MG 1, with overload protection, sized to start,
accelerate, and operate door in either direction, from any
position, at not less than 2/3 fps (0.2 m/s) and not more than
1 fps (.03m/s), without exceeding nameplate ratings or
considering service factor.
** NOTE TO SPECIFIER ** Delete one of the following types.
1.
Type: Mechanical.
2.
Type: Solid State.
** NOTE TO SPECIFIER ** Delete one of the following types.
3.
Type: Jackshaft.
4.
Type: Trolley.
5.
HP:
** NOTE TO SPECIFIER ** Delete all but one of the following types.
a.
1/3 hp (246 W).
b.
1/2 hp (373 W).
c.
3/4hp (559 W).
d.
1 hp (746 W).
1.
Power Characteristics:
** NOTE TO SPECIFIER ** Delete voltage and phase not required.
a.
115 V.
b.
220 V.
c.
460 V.
d.
1 phase.
e.
3 phase.
1.
Service Factor:
** NOTE TO SPECIFIER ** Delete NEMA types not required.
a.
NEMA MG 1.
b.
NEMA 4 watertight.
c.
NEMA 9 waterproof.
d.
NEMA 10 oil resistant.
e.
NEMA 12 explosion resistant.
1.
Coordinate wiring requirements and electrical
characteristics of motors with building electrical system.
** NOTE TO SPECIFIER ** Delete one of the following types of remote
control station contacts.
F.
Remote Control Station: Provide momentary contact, 3-button
control station with push - button controls labeled "Open",
"Close" and "Stop".
G.
Remote Control Station: Provide continuous contact, 3-button
control station with push - button controls labeled "Open",
"Close" and "Stop".
H.
Provide interior units, fully guarded, surface mounted,
heavy-duty type, with general-purpose NEMA ICS 6 enclosure in
one of the following types:
** NOTE TO SPECIFIER ** Delete all but one of the following enclosure
types.
1.
Enclosure Type: Type 1.
2.
Enclosure Type: Type 4.
3.
Enclosure Type: Type 12.
A.
Obstruction Detection Device: Provide each motorized door with
indicated external automatic safety sensor able to protect
full width of door opening. Activation of sensor immediately
stops and reverses downward door travel.
** NOTE TO SPECIFIER ** Delete the safety options not required.
1.
Sensor Edge: Provide each motorized door with an automatic
safety sensing edge, located within astragal or weather
stripping mounted to bottom bar. Contact with sensor
immediately stops and reverses downward door travel. Connect
to control circuit using manufacturer's standard take-up
reel or self-coiling cord. Sensing edge shall be operated
by:
** NOTE TO SPECIFIER ** Delete all but one of the following types.
a.
Electric.
b.
Pneumatic.
c.
Electric Fail safe.
d.
Pneumatic Fail safe.
1.
Photo-electric control: Provide each motorized door with a
photo-electric device that will stop and reverse the
downward door travel if the light beam is broken or blocked.
Device shall be:
** NOTE TO SPECIFIER ** Delete one of the following types.
a.
NEMA Type 1.
b.
NEMA Type 4.
A.
Limit Switches: Provide adjustable switches, interlocked with
motor controls and set to automatically stop door at fully
opened and fully closed positions.
** NOTE TO SPECIFIER ** Delete option below if not required.
K.
Radio Controls: Provide 3 button radio transmitter to provide
remote open, close, stop functionality.
1.
Provide external antenna and coaxial wiring to receiver to
enhance radio control reception.
** NOTE TO SPECIFIER ** Delete optional safety feature below if not
desired. Not commonly used with drawbar type openers.
L.
Provide auxiliary chain hoist: for emergency manual operation
while disconnecting motor, without affecting timing of limit
switch. Mount disconnect and operator so they are accessible
from floor level. Include interlock device to automatically
prevent motor from operating when emergency operator is
engaged.
3.
EXECUTION
1.
EXAMINATION
A.
Examine wall and overhead areas, including opening framing
and blocking, with installer present, for compliance with
requirements for installation tolerances, clearances, and
other conditions affecting performance of Work in this
Section.
1.
Proceed with installation only after unsatisfactory
conditions have been corrected.
B.
If substrate preparation is the responsibility of another
installer, notify Architect of unsatisfactory preparation
before proceeding.
2.
PREPARATION
A.
Prepare surfaces using the methods recommended by the
manufacturer for achieving the best result for the
substrate under the project conditions.
3.
INSTALLATION
A.
Install overhead doors and track in accordance with
approved shop drawings and the manufacturer's printed
instructions.
4.
PROTECTION
A.
Protect installed products until completion of project.
B.
Touch-up, repair or replace damaged products before
Substantial Completion.
END OF SECTION
08360-5

  • L SKIM PENELITIAN PEMULA RECTANGLE 5 APORAN PENELITIAN
  • Q1 FIGURE 1 SHOWS A FISH CALLED A CARP
  • CONTACTTGSLAWVN TEL 19006110 – FAX 0473005720 SỐ 9 NGÁCH
  • THE PLACENAMES OF STIFFORD RECORDER MJ SAUNDERS ESSEX PLACENAMES
  • ¿QUÉ LE DEJA LA FORESTACIÓN A LA GENTE? OTRO
  • SEZNAM VĚDECKÝCH A ODBORNÝCH PRACÍ UČEBNIC A UČEBNÍCH TEXTŮ
  • OSCAR LUIS CASTAÑEDA LOSSIO Ó SCAR LUIS CASTAÑEDA LOSSIO
  • UNIVERSIDAD DE DUSSELDORF LOS ESTUDIOS DE “GOBIERNO Y CONTROL
  • 33 ‘MEN CRY TOO’ BLACK MASCULINITIES AND THE FEMINIZATION
  • 137 STATE OF ARKANSAS PROCUREMENT LAW AND RULES SEPTEMBER
  • 94 TRANSLOCATION SUPPORT OCR BIOLOGY A TRANSLOCATION SPECIFICATION REFERENCE
  • OPEN INFORMAL SESSION OF THE UNITED NATIONS INTERAGENCY
  • Cuadros%20intensidad%20tr%C3%A1fico
  • “ANTES DE LA MEDIANOCHE” EEUU 2013 DIR RICHARD LINKLATER
  • LA PRIMERA FAMILIA NORTEAMERICANA MARIANO RAJOY Y SU FAMILIA
  • VEILEDNING FOR TILTAKSHAVER SØKER OG NABOER 10 JUNI 2015
  • CORNELL DAIRY SCIENCE FACTS U N I V
  • DERECHO INTERNACIONAL TEMAS DE EXAMEN – CUESTIONARIO 1 EXPRESE
  • CONTENIDO EN ALÉRGENOS DE CADA PLATO [INCLUYA AQUÍ EL
  • C463 PÁGINA 12 S C463 ORIGINAL INGLÉS FECHA 24
  • NO TENEMOS QUE TENER VERGÜENZA POR LA CALLE LOS
  • CURRICULUM VITAE RAMEY LAURA RIEGER 14 SEPTEMBER 1959
  • BIL 3800 TYP CONCURRENT RESOLUTION CR INB HOUSE IND
  • OFFICIAL PLAN – VOLUME II 2 JENNINGS CREEK COMMUNITY
  • LA ESTIMULACIÓN TEMPRANA ENFOQUES PROBLEMÁTICAS Y PROYECCIONES DR FRANKLIN
  • PRESSMEDDELANDE LA VIE ET L´AMOUR ÄR TITELN PÅ EN
  • EHH CLIENT FILE CHECKLIST CLIENT NAME PROGRAM
  • UNIVERSIDAD DE SAN MARTIN DE PORRES CONTABILIDAD
  • GOVERNMENTAL INSTITUTIONS VS ASSOCIATIONS THE MULTIFACETED EXPRESSION OF SIDDHA
  • EKSTRA – 2 JUNI 2009 NYHEDSBREV FRA HOSPITALSLEDELSEN