unit description air-cooled series r helical-rotary liquid chiller model rtac 120 to 400 (400 to 1500 kw –
Unit
Description
Air-cooled Series R Helical-Rotary Liquid Chiller
Model RTAC 120 to 400
(400 to 1500 kW – 50 Hz)
RLC-PRG002-E4
-------------
CG-PRGXXX-E4
------------
Chiller description
===================
*
R134a refrigerant
*
Two refrigerant circuits
*
Able to unload down to 15% of full load
*
Semi-hermetic horizontal helical rotary compressor(s)
*
One shell and tube evaporator of falling film type
*
Electronic expansion valves
*
One water inlet connection and one water outlet connection
*
One single main power supply for all the chiller
*
Microprocessor based control with user interface
*
Rated and certified in accordance with Eurovent standards
*
Compliant with EC requirements for machinery, electromagnetic and
Pressure Equipment Directive or with national legislations.
Construction characteristics
============================
*
Entirely painted – must withstand 500 hours minimum in a
salt-spray fog test
*
Weatherproof electrical panels
*
Entire coil protected for shipment and rigging
Compressor characteristics
==========================
*
Semi-hermetic horizontal helical-rotary type
*
Direct drive – maximum speed of screw : 3000 RPM at 50 Hz
*
Two rotors in the same horizontal plane
*
Suction gas-cooled motor
*
Oil lubrication by refrigerant pressure differential between HP
and LP
*
Continuous load control by slide valve actuated by oil pressure
*
Star-delta starter
*
Integrated oil filter
Evaporator characteristics
==========================
*
Shell and tube – Falling film type
*
Freeze protection by trace heater
*
Grooved pipes water connections for Victaulic couplings
Condenser
---------
*
Aluminium slit fins mechanically bonded to copper tubes
*
Circuiting including subcooling
Fans
====
*
Fan blades in composite material
*
Class F, IP55 motor
*
Motor with permanently lubricated ball bearings
Refrigerant circuit
*
Two refrigerant circuits - with one or two manifolded compressors
on each
*
Per circuit :
*
Liquid line shut-off valve
*
Replaceable core filter dryer
*
Electronic expansion valve
*
Charging valve
*
Discharge and oil line check valves
*
Full operating charge of R134a refrigerant and oil
Electrical panel
================
*
Fully mounted and wired in factory
*
Weatherproof
*
Full opening access doors
*
Lockable through-the-door disconnect switch
*
One star-delta closed transition starter per compressor fully
factory-mounted and wired
*
One single main power supply for the complete chiller (power and
control)
*
Primary and secondary fused control power transformer
Control system
==============
*
Microprocessor based – Proportional and Integral type
*
User interface displaying full messages in clear language
*
Access to all control and safety parameters through different
menus
*
Ensures :
*
Load control
*
Fault detection
*
Start-up of compressors and fans
*
Diagnostic and supervision
*
Takes corrective actions to prevent shutdown due to abnormal high
and low pressure and overcurrent
*
Possibility of direct interconnection with a building management
system using LonTalk™ open communication protocol
- 3 - RLC-PRG002-E4